| FUNCTION DESCRIPTION |
SPECIFICATIONS |
| POWER INPUT |
RATED INPUT VOLTAGE (V) |
1PH 220V (-15%) -240V (+10%) |
| 1PH 220V (-15%) -240V (+10%) |
| 1PH 220V (-15%) -240V (+10%) |
| RATED INPUT CURRENT(A) |
REFER TO “RATED VALUE” |
| RATED FREQUENCY (HZ) |
50HZ OR 60HZ, PERMISSIBLE RANGE: 47~63HZ |
| POWER OUTPUT |
RATED MOTOR CAPACITY (KW) |
REFER TO “RATED VALUE” |
| RATED OUTPUT (KVA) |
REFER TO “RATED VALUE” |
| RATED CURRENT (A) |
REFER TO “RATED VALUE” |
| RATED OUTPUT VOLTAGE (V) |
EQUAL TO INPUT VOLTAGE WITH LESS THAN 5% ERROR |
| TECHNICAL CONTROL PERFORMANCE |
CONTROL MODE |
SVPWM, SVC |
| MOTOR TYPE |
ASYNCHRONOUS MOTOR |
| SPEED RANGE |
1:100 |
| SPEED CONTROL PRECISION |
± 0.2% (SVC) |
| SPEED FLUCTUATION |
± 0.3% (SVC) |
| TORQUE RESPONSE |
<20MS (SVC) |
| TORQUE CONTROL PRECISION |
10% |
| STARTING TORQUE |
0.5HZ 150% (SVC) |
| OVERLOAD CAPACITY |
1M FOR 150% OF RATED CURRENT, 10S FOR 180% OF RATED CURRENT, 1S FOR 200% OF RATED CURRENT150% |
| RUNNING CONTROL CHARACTERISTICS |
FREQUENCY SETUP MODE |
KEYPAD DIGITS, ANALOG QUANTITY, PULSE FREQUENCY, MULTI-STEP SPEED OPERATION, SIMPLE PLC, PID, MODBUS COMMUNICATION. REALIZE SWITCHING BETWEEN THE SET COMBINATION AND THE SET CHANNEL. |
| REALIZE SWITCHING BETWEEN THE SET COMBINATION AND THE SET CHANNEL. |
| AUTO VOLTAGE ADJUSTMENT |
KEEP THE OUTPUT VOLTAGE CONSTANT WHEN GRID VOLTAGE CHANGES. |
| FAULT PROTECTION |
PROVIDE ALL-AROUND FAULT PROTECTION: OVERCURRENT, OVERVOLTAGE, UNDERVOLTAGE, OVERHEAT, PHASE LOSS AND OVERLOAD |
| SPEED TRACKING RESTART |
REALIZE IMPACT-FREE SMOOTH STARTUP OF ROTATING MOTOR |
| AI |
ONE (AI2) 0~10V/0~20MA, ONE (AI3) -10~10V |
| AO |
TWO (AO1, AO2) 0~10V /0~20MA |
| DI |
FOUR NORMAL INPUTS, MAX FREQUENCY: 1KHZ |
| ONE HIGH SPEED INPUT, MAX FREQUENCY 50KHZ |
| DO |
ONE Y1 TERMINAL OUTPUT, TWO PROGRAMMABLE RELAY OUTPUTS |
| RELAY OUTPUT |
TWO PROGRAMMABLE RELAY OUTPUTS |
| RO1A NO, RO1B NC, RO1C COMMON PORT |
| RO2A NO, RO2B NC, RO2C COMMON PORT |
| CONTACT CAPACITY:3A/AC250V |
| OTHERS |
DC REACTOR |
18.5KW AND ABOVE MODELS CARRY BUILT-IN DC REACTOR IN STANDARD CONFIGURATION |
| INSTALLATION MODE |
1PH 220V/3PH 380V AND BELOW AND 3PH 220V 0.75KW AND BELOW SUPPORT RAIL-TYPE AND WALL-TYPE INSTALLATION; |
| 3PH 380V 4KW AND ABOVE AND 3PH 220V 1.5KW AND ABOVE SUPPORT WALL-TYPE AND FLANGE-TYPE INSTALLATION; |
| BRAKE UNIT |
BUILT-IN IN STANDARD CONFIGURATION FOR 37KW AND BELOW MODELS AND OPTIONAL FOR 45~110KW MODELS; |
| EMC FILTER |
BUILT-IN C3 FILTER IS OPTIONAL FOR 3PH 380V 4KW AND ABOVE, 3PH 220V 1.5KW AND ABOVE |
| OPTIONAL FILTER: IEC61800-3 C2, IEC61800-3 C3 |
| AMBIENT TEMP |
10~50 celcius, DERATE IF THE AMBIENT TEMP IS ABOVE 40 celcius |
| ELEVATION |
BELOW 1000M, DERATE IF THE ELEVATION IS ABOVE 1000M, DERATE BY 1% PER EVERY ADDITIONAL 100M |
| PROTECTION LEVEL |
IP20 |
| NOTE: THE INVERTER WITH PLASTIC SHELL SHOULD BE INSTALLED IN THE METAL DITRIBUTION BOX WHICH COMPLIES WITH IP20 AND IP3X |
| SAFETY |
MEET CE REQUIREMENT |
| COOLING MODE |
AIR COOLING |